Modbus TCP/FF HSE to FOUNDATION Fieldbus H1 Gateway

Integration of up to 4 FF H1 segments into control systems via Modbus TCP or FOUNDATION Fieldbus HSE

FF Network Integration via Modbus Including Redundancy

With Softing’s FG-200FF, you can easily integrate up to four FOUNDATION™ Fieldbus (FF) H1 links into control systems supporting Modbus. The Softing FG-200FF provides redundancy and is suitable for use in ATEX zone. This device features fast access to process data, while making use of Fiedbus Foundation (FF) advantages like reduced cabling, central field device parameterization, comprehensive diagnostics, or intrinsically safe device segments. The Fieldbus foundation gateway (FG-200FF) is fully compatible with the R. STAHL bus-Carrier Series 9419 and Fieldbus Power Supply Series 9412 products for a very easy commissioning.

Easy Commissioning with the FG-200FF

  • Optional support of R. STAHL bus-Carrier Series 9419 and Fieldbus Power Supply 9412 products (cabling reduced to a minimum)
  • Modbus data import to web server reducing mapping efforts

Easy Asset Management thanks to the FG-200FF

  • Visitor mode avoiding interference with network behavior
  • Enabling asset management systems (e.g. Emerson’s AMS) and Field Device Tool (FDT) frame applications (e.g. SMART VISION, FieldMate, Field Device Manager, FieldCare, or PACTware)

The FG-200FF gateway makes easy the device redundancy

  • Redundancy link enabling device redundancy (D-3 according to FF-593)
  • Automatic mirroring of configuration data
  • Very fast redundancy switch-over between 2* FG-200FF Fieldbus foundation Gateway

All Necessary Tools Included

  • FF Configuration Tool for configuration of devices and cyclic communication
  • PACTware for device configuration and basic asset management tasks

FG-200FF vs FG-100FF

FG-110 FG-200
CPU PowerPC 805T 100 MHz Cortex A9 400 MHz
H1 Interface (MAU) Inductive coupling (no bus power required) Bus-powered (10 mA drawn from bus)
Ethernet Ports 1 2 (medium redundancy, same IP address)
Redundancy Communication Serial Link (115,2 kBit/s) and Ethernet Serial Link (1 MBit/s) only, no load on Ethernet
Cabling All connectors on front side Fieldbus: bottom
Ethernet: front
Power: top or power bus in DIN rail
Mechanical Compatibility STAHL bus carrier
Dimensions 131 mm x 47 mm x 111 mm 100 mm x 35 mm x 105 mm (- 46%)

Compatibility

Functionality Comments
Host Interface
Device Interface
Engineering Existing projects can be downloaded without any changes
Mechanical Dimensions Smaller in each dimension: Same cabinet can be used
Bus Power Supply 10 mA required per Link (same as for all devices and most host systems)
FISCO Power Supplies with separate host interface must provide 10 mA on host side
Cabling Different positions, different connectors: Cables have to be modified
Redundancy Management FG-100/FG-110 and FG-200 cannot cooperate as redundant pair: No replacement of FG-110 by FG-200 in run possible. Complete redundant pair of Linking Devices has to be replaced at same time.
Hardware Processor
Status LEDs (Gateway)

Status LEDs (Fieldbus)
Altera Cyclone V SoC with dual-core ARM Cortex-A9
PWR (power supply), RUN (operation), ERR (error), RDL (redundancy link)
FF H1 activity per link
Interfaces and Connectors Ethernet


FOUNDATION fieldbus H1
2 * IEEE 802.3 100BASE-TX / 10BASE-T (only ETH1 supported)
Connectors: RJ45
4 FF H1 links, compliant to type 114 of FF physical layer profile
(each link capable to operate independently as Link Master and/or Time Master)
Transfer rate: 31.25 Kbit/s
Fieldbus voltage range: 9 VDC ... 32 VDC, preferred voltage: 24 VDC
Current consumption: 10 mA / link
Connectors: 3-position screw connection, galvanically isolated
Physical Properties Dimensions (H x W x D)
Weight
Power Supply






Operating / Storage Temperature
Relative Humidity
Cooling
Coating
Mounting
Protection Class
100 mm x 35 mm x 105 mm
Approx. 0.25 kg
18 VDC ... 32 VDC; SELV/PELV power supply mandatory
Typical input current: 200 mA, maximum input current: 1 A (allowing for in-rush current at switch-on)
No power supply to FF H1 links through FG-200 HSE/FF Modbus
-40 °C .. +70 °C / -40 °C .. +85 °C
(see detailed mounting description in user manual)
10 % ... 95 %, non-condensing
Convection, no fan
Conformal coating based on ANSI / ISA-S71.04 G3
DIN rail 35 mm
IP20
Software Protocols


Redundancy
FOUNDATION fieldbus H1
FOUNDATION fieldbus HSE
Modbus TCP
Device redundancy compliant to type D-3 according to specification FF-593
Conformity / Certifications CE

Electromagnetic Compatibility (EMC)


Vibration / Shock

Hazardous Location Certifications


Safety Requirements
EN61000-6-2, EN61000-6-4, EN55022 Limit Class A, EN55011
FCC CFR45, Part 15 Section 15.107 and 15.109 (Class A),
VCCI Class A Information Technology Equipment 2002
DIN EN 60068-2-6 Vibration / DIN EN 60068-2-27 Shock
cULus: Class 1, Division 2, Groups A, B, C, D (in preperation)
IECEx: Ex nA [ic] IIC T4 Gc
ATEX: II 3G nA [ic] IIC T4 Gc
IEC/EN/UL 61010-1
IEC/EN/UL 61010-2-201 (with CB scheme)

Scope of Delivery

Hardware FG-200 HSE/FF Modbus
Software FF Configuration Tool, FDT CommDTM, PACTware on CD-ROM
Documentation Quick Startup Guide, User Manual on CD-ROM

Order Numbers

 

GCL-EK-024100 FG-200 HSE/FF Modbus
GCL-EK-024101 FG-200 HSE/FF Modbus, functionally identical design variant for use with R. STAHL bus-Carrier Series 9419 and Fieldbus Power Supply 9412 products

For training , please contact us

People looking at this product may be also interested in :

I am text block. Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.