Modbus TCP/FF HSE to FOUNDATION Fieldbus H1 Gateway
Integration of up to 4 FF H1 segments into control systems via Modbus TCP or FOUNDATION Fieldbus HSE

FF Network Integration via Modbus Including Redundancy
With Softing’s FG-200FF, you can easily integrate up to four FOUNDATION™ Fieldbus (FF) H1 links into control systems supporting Modbus. The Softing FG-200FF provides redundancy and is suitable for use in ATEX zone. This device features fast access to process data, while making use of Fiedbus Foundation (FF) advantages like reduced cabling, central field device parameterization, comprehensive diagnostics, or intrinsically safe device segments. The Fieldbus foundation gateway (FG-200FF) is fully compatible with the R. STAHL bus-Carrier Series 9419 and Fieldbus Power Supply Series 9412 products for a very easy commissioning.

Easy Commissioning with the FG-200FF
- Optional support of R. STAHL bus-Carrier Series 9419 and Fieldbus Power Supply 9412 products (cabling reduced to a minimum)
- Modbus data import to web server reducing mapping efforts
Easy Asset Management thanks to the FG-200FF
- Visitor mode avoiding interference with network behavior
- Enabling asset management systems (e.g. Emerson’s AMS) and Field Device Tool (FDT) frame applications (e.g. SMART VISION, FieldMate, Field Device Manager, FieldCare, or PACTware)
The FG-200FF gateway makes easy the device redundancy
- Redundancy link enabling device redundancy (D-3 according to FF-593)
- Automatic mirroring of configuration data
- Very fast redundancy switch-over between 2* FG-200FF Fieldbus foundation Gateway
All Necessary Tools Included
- FF Configuration Tool for configuration of devices and cyclic communication
- PACTware for device configuration and basic asset management tasks
FG-200FF vs FG-100FF
FG-110 | FG-200 | |
---|---|---|
CPU | PowerPC 805T 100 MHz | Cortex A9 400 MHz |
H1 Interface (MAU) | Inductive coupling (no bus power required) | Bus-powered (10 mA drawn from bus) |
Ethernet Ports | 1 | 2 (medium redundancy, same IP address) |
Redundancy Communication | Serial Link (115,2 kBit/s) and Ethernet | Serial Link (1 MBit/s) only, no load on Ethernet |
Cabling | All connectors on front side | Fieldbus: bottom Ethernet: front Power: top or power bus in DIN rail |
Mechanical Compatibility | STAHL bus carrier | |
Dimensions | 131 mm x 47 mm x 111 mm | 100 mm x 35 mm x 105 mm (- 46%) |
Compatibility
Functionality | Comments | |
---|---|---|
Host Interface | ✔ | |
Device Interface | ✔ | |
Engineering | ✔ | Existing projects can be downloaded without any changes |
Mechanical Dimensions | ✔ | Smaller in each dimension: Same cabinet can be used |
Bus Power Supply | ❍ | 10 mA required per Link (same as for all devices and most host systems) FISCO Power Supplies with separate host interface must provide 10 mA on host side |
Cabling | ✖ | Different positions, different connectors: Cables have to be modified |
Redundancy Management | ✖ | FG-100/FG-110 and FG-200 cannot cooperate as redundant pair: No replacement of FG-110 by FG-200 in run possible. Complete redundant pair of Linking Devices has to be replaced at same time. |
Hardware | Processor Status LEDs (Gateway) Status LEDs (Fieldbus) | Altera Cyclone V SoC with dual-core ARM Cortex-A9 PWR (power supply), RUN (operation), ERR (error), RDL (redundancy link) FF H1 activity per link |
Interfaces and Connectors | Ethernet FOUNDATION fieldbus H1 | 2 * IEEE 802.3 100BASE-TX / 10BASE-T (only ETH1 supported) Connectors: RJ45 4 FF H1 links, compliant to type 114 of FF physical layer profile (each link capable to operate independently as Link Master and/or Time Master) Transfer rate: 31.25 Kbit/s Fieldbus voltage range: 9 VDC ... 32 VDC, preferred voltage: 24 VDC Current consumption: 10 mA / link Connectors: 3-position screw connection, galvanically isolated |
Physical Properties | Dimensions (H x W x D) Weight Power Supply Operating / Storage Temperature Relative Humidity Cooling Coating Mounting Protection Class | 100 mm x 35 mm x 105 mm Approx. 0.25 kg 18 VDC ... 32 VDC; SELV/PELV power supply mandatory Typical input current: 200 mA, maximum input current: 1 A (allowing for in-rush current at switch-on) No power supply to FF H1 links through FG-200 HSE/FF Modbus -40 °C .. +70 °C / -40 °C .. +85 °C (see detailed mounting description in user manual) 10 % ... 95 %, non-condensing Convection, no fan Conformal coating based on ANSI / ISA-S71.04 G3 DIN rail 35 mm IP20 |
Software | Protocols Redundancy | FOUNDATION fieldbus H1 FOUNDATION fieldbus HSE Modbus TCP Device redundancy compliant to type D-3 according to specification FF-593 |
Conformity / Certifications | CE Electromagnetic Compatibility (EMC) Vibration / Shock Hazardous Location Certifications Safety Requirements | EN61000-6-2, EN61000-6-4, EN55022 Limit Class A, EN55011 FCC CFR45, Part 15 Section 15.107 and 15.109 (Class A), VCCI Class A Information Technology Equipment 2002 DIN EN 60068-2-6 Vibration / DIN EN 60068-2-27 Shock cULus: Class 1, Division 2, Groups A, B, C, D (in preperation) IECEx: Ex nA [ic] IIC T4 Gc ATEX: II 3G nA [ic] IIC T4 Gc IEC/EN/UL 61010-1 IEC/EN/UL 61010-2-201 (with CB scheme) |
-
Drivers & Software
-
Manuals & Documentation
- FG-200 HSE/FF Modbus User Manual V1.20 ( Version: EN-012018-1.20)
- FG-200 HSE/FF Modbus Quick Startup Guide V1.31 ( Version: EN-102018-1.31 )
- Communication Configuration Tool User Guide V2.23
- Firmware V1.20.01.4262
-
Articles & White Papers
-
Certificates
-
Data Sheets
- CD ( ISO)
Scope of Delivery
Hardware | FG-200 HSE/FF Modbus |
Software | FF Configuration Tool, FDT CommDTM, PACTware on CD-ROM |
Documentation | Quick Startup Guide, User Manual on CD-ROM |
Order Numbers
GCL-EK-024100 | FG-200 HSE/FF Modbus |
GCL-EK-024101 | FG-200 HSE/FF Modbus, functionally identical design variant for use with R. STAHL bus-Carrier Series 9419 and Fieldbus Power Supply 9412 products |
For training , please contact us
Video available on howto use the FG-200FF
- FG-200 FF : Adaptation Of the Modbus mapping generated by Communication Configurator Software ( mp4)
- FG-200 FF : Creation of a configuration based on a network scan (mp4)
- FG-200FF : Integrate and use the FG-200 gateway with AMS device manager ( mp4 )
- FG-200FF : Access FF H1 Device Parameters via Modbus with FG-200 ( mp4 )
- Power Conditionner : STAHL : 9412 ( 9412/00-310-11s )
- ACA-ZZ-020631 : Redundancy Link (3-pole), Cable (30 cm) for connecting redundant pairs of FG-200
Documentations :
I am text block. Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.